Description

Product Description

This KNX line coupler connects two KNX twisted-pair segments, such as a main line and a sub-line, with galvanic isolation between them and support for long KNX frames. It is powered only from the KNX bus on the main line, so no external supply is needed.

The physical address selects line coupler, area coupler or repeater operation; in repeater mode the ETS filter settings have no effect. Routing for group, individually addressed and broadcast telegrams can be set to block, filter or forward in each direction. As supplied, individually addressed telegrams are filtered and group telegrams are blocked. Each device carries a certificate with its serial number and factory setup key, printed on the device and encoded in a QR code.

The coupler mounts on a DIN rail, is 1 TE (18 mm) wide, 60 mm deep and 90 mm high, and has an IP20 enclosure rating. It operates from -5 to +45 °C.